Power electronics, drives, transformers and batteries inside a cabinet convert part of their input energy into heat. Without active thermal management, internal temperature rises until components derate, age prematurely or trip. Forcing ambient air with a fan solves heat but admits dust and humidity; a closed-loop cabinet air conditioner cools the internal air while the enclosure stays sealed at IP55, protecting sensitive equipment in harsh environments.
A cabinet AC is a self-contained refrigeration loop mounted on the enclosure wall. Internal air passes over the cold evaporator; heat is pumped to the external condenser and rejected outdoors. Key elements:
Total cooling demand is the sum of internal heat and envelope heat gain:
Q_total = Q_internal + Q_envelope
Worked example. A 0.6 m³ cabinet (≈800×600×1200 mm, A≈5.5·V2/3≈4.3 m²), internal load 450 W, ambient 50 °C, target 35 °C, bare steel (U=6.0): Q_envelope = 6.0 × 4.3 × 15 ≈ 387 W; Q_total ≈ 837 W; with a 1.3 safety factor the required capacity is ≈1088 W — a small HCK unit covers it. For larger drives or hotter sites, step up to 3000–7500 W.
| Model | Cooling capacity | Supply | Protection | Operating range | Refrigerant | Comms |
|---|---|---|---|---|---|---|
| HCK-2000* | ≈2000 W | 220 V ±10% 50 Hz / 48 V DC opt. | IP55 | −40…+55 °C | R410A | RS485 |
| HCK-3000 | ≈3000 W | 220 V ±10% 50 Hz / 48 V DC opt. | IP55 | −40…+55 °C | R410A | RS485 |
| HCK-3500 | ≈3500 W | 220 V ±10% 50 Hz / 48 V DC opt. | IP55 | −40…+55 °C | R410A | RS485 |
| HCK-5000 | ≈5000 W | 220 V ±10% 50 Hz / 48 V DC opt. | IP55 | −40…+55 °C | R410A | RS485 |
| HCK-7500 | ≈7500 W | 220 V ±10% 50 Hz / 48 V DC opt. | IP55 | −40…+55 °C | R410A | RS485 |
Energy-storage cabin (储能舱) Prefabricated substation / cabin (预制舱) Telecom base station (基站) EV charging cabinet (充电桩) Mining site (矿山) Offshore / marine (海上)
All share the same need: keep sealed enclosures within component limits where dust, salt, humidity and temperature extremes would defeat passive cooling. HCK units are built for IP55, wide-temperature and corrosive atmospheres.
| Criterion | Cabinet AC (HCK) | Air-to-air heat exchanger | Filtered fan |
|---|---|---|---|
| Sealing / IP | IP55 closed loop | IP55 (no active cooling of hot days) | IP low (open) |
| Cooling below ambient | Yes (refrigeration) | No (limited by ambient) | No |
| Dust / humidity exclusion | Excellent | Good | Poor |
| Recommended use | Harsh / hot / sealed | Mild climate, low ΔT | Clean, cool indoor |
A: Yes — 48 V DC supply option is available alongside 220 V ±10% 50 Hz.
A: HCK cabinet air conditioners are CE-marked; certification documentation is provided. (Confirm latest status per model.)
A: Yes — voltage, dimensions, coating, communication and branding can be tailored.
A: RS485 / Modbus exposes temperature, alarms and run state to plant BMS/SCADA.
HCK units use a rotary compressor, R410A refrigerant and a high-efficiency motor, with component sourcing documented per project. Products are CE-marked and offered as OEM/ODM.
Zhejiang Haocheng Industrial Control Equipment Co., Ltd. (brand HCK) designs and manufactures cabinet, box-type and prefabricated-cabin air conditioners from 2000 to 7500 W. Visit www.zjhcc.com or contact the engineering team for selection support.