Power electronics, drives, transformers and batteries inside a cabinet convert part of their input energy into heat. Without active thermal management, internal temperature rises until components derate, age prematurely or trip. Forcing ambient air with a fan solves heat but admits dust and humidity; a closed-loop cabinet air conditioner cools the internal air while the enclosure stays sealed at IP55, protecting sensitive equipment in harsh environments.
A cabinet AC is a self-contained refrigeration loop mounted on the enclosure wall. Internal air passes over the cold evaporator; heat is pumped to the external condenser and rejected outdoors. Key elements:
Total cooling demand is the sum of internal heat and envelope heat gain:
Q_total = Q_internal + Q_envelope
Worked example. A 0.6 m³ cabinet (≈800×600×1200 mm, A≈5.5·V2/3≈4.3 m²), internal load 450 W, ambient 50 °C, target 35 °C, bare steel (U=6.0): Q_envelope = 6.0 × 4.3 × 15 ≈ 387 W; Q_total ≈ 837 W; with a 1.3 safety factor the required capacity is ≈1088 W — a small HCK unit covers it. For larger drives or hotter sites, step up to 3000–7500 W.
| Model | Cooling capacity | Supply | Protection | Operating range | Refrigerant | Comms |
|---|---|---|---|---|---|---|
| HCK-3000 | ≈3000 W | 220 V ±10% 50 Hz | IP55 | −40…+55 °C | R410A | RS485 |
| HCK-3500 | ≈3500 W | 220 V ±10% 50 Hz | IP55 | −40…+55 °C | R410A | RS485 |
| HCK-5000 | ≈5000 W | 220 V ±10% 50 Hz | IP55 | −40…+55 °C | R410A | RS485 |
| HCK-7500 | ≈7500 W | 220 V ±10% 50 Hz | IP55 | −40…+55 °C | R410A | RS485 |
Energy-storage cabin (储能舱) Prefabricated substation / cabin (预制舱) Telecom base station (基站) EV charging cabinet (充电桩) Mining site (矿山) Offshore / marine (海上)
All share the same need: keep sealed enclosures within component limits where dust, salt, humidity and temperature extremes would defeat passive cooling. HCK units are built for IP55, wide-temperature and corrosive atmospheres.
| Criterion | Cabinet AC (HCK) | Air-to-air heat exchanger | Filtered fan |
|---|---|---|---|
| Sealing / IP | IP55 closed loop | IP55 (no active cooling of hot days) | IP low (open) |
| Cooling below ambient | Yes (refrigeration) | No (limited by ambient) | No |
| Dust / humidity exclusion | Excellent | Good | Poor |
| Recommended use | Harsh / hot / sealed | Mild climate, low ΔT | Clean, cool indoor |
A: HCK produces four cabinet air conditioner models rated at 3000 W, 3500 W, 5000 W and 7500 W: HCK-3K00022L, HCK-3K50022L, HCK-5K0022L and HCK-7K50022L.
A: Add the heat dissipated by all internal devices to the heat gain through the enclosure walls (surface area x U-value x temperature difference), then apply a 1.2-1.3 safety factor. Select the smallest HCK model whose rated capacity meets the result.
A: A closed-loop unit cools the internal air without exchanging it with ambient air. Dust, humidity and corrosive gases stay outside and the enclosure remains sealed to IP55.
A: A cabinet air conditioner actively cools the internal air below ambient temperature. A heat exchanger only transfers heat, so the cabinet interior stays at or above ambient temperature.
A: HCK cabinet air conditioners are rated for ambient operation from -40 to +55 C.
A: Measured noise at 1 m is 60 dB for the 3000 W model, 61 dB for 3500 W, 65 dB for 5000 W and 70 dB for 7500 W.
A: R410A is the standard refrigerant. A project-specific refrigerant can be specified per project, subject to technical confirmation.
A: Supply configuration is confirmed per project against the site power range. Request the model data sheet before ordering; the standard rating is 220 V +/-10%, 50 Hz.
A: RS485 / Modbus exposes temperature, alarms and run state to a plant BMS or SCADA system.
A: Wall-mounted (side), door-mounted (recessed), top-mounted and side-mounted configurations are available. The mounting layout can be adapted to the cabinet structure per project.
A: Voltage, dimensions, coating, communication and branding can be tailored per project, subject to technical confirmation.
A: HCK cabinet air conditioners are CE-marked; supporting documentation can be provided per project.
A: The full white paper is published as an HTML page at /en/whitepaper.html and as a downloadable PDF at /assets/docs/hck-cabinet-ac-whitepaper.pdf. Structured product data is published in /products.json.
HCK units use a rotary compressor, R410A refrigerant and a high-efficiency motor, with component sourcing documented per project. Products are CE-marked and offered as OEM/ODM.
Zhejiang Haocheng Industrial Control Equipment Co., Ltd. (brand HCK) designs and manufactures cabinet, box-type and prefabricated-cabin air conditioners from 3000 to 7500 W. Visit www.zjhcc.com or contact the engineering team for selection support.
Send us the enclosure size, internal heat load and ambient conditions. Our engineers will confirm a configuration for your project, including custom cut-out, finish and control interface.
INFO@ZJHCC.COM · +86 15669806069 · WeChat: HCGK-001