The most common sizing mistake is treating the heat generated inside a cabinet as the cooling capacity you need to buy. Between the two sit solar gain, wall conduction and a safety margin. Here is one complete small-cabinet example. Note first: the 2000 W below is a calculated total heat load, not a unit model. HCK production cabinet air conditioners are 3000, 3500, 5000 and 7500 W.
1. Scenario and known conditions
An outdoor control cabinet holding a PLC, drives and switched-mode power supplies, about 0.8 m³. Peak ambient is 40 °C. The enclosure is light-coloured and shaded, but the west face takes direct afternoon sun. Internal temperature must stay at or below 45 °C.
2. The three sources of heat load
- Internal dissipation: PLC, drives and power supplies, counted at 60–80% of nameplate draw.
- Solar gain: a sunlit square metre can add several hundred watts; light colours and shading cut this sharply.
- Wall conduction: the larger the ambient-to-internal difference and the tighter the seal, the steadier the heat entering through the walls.
3. The example: add the three up
| Source | Value |
|---|---|
| Internal dissipation | 900 W |
| Solar gain (west face) | 650 W |
| Wall conduction (40 °C ambient) | 450 W |
| Total heat load | 2000 W |
The 2000 W here is the total heat load produced by the example, used to show the sizing method. It is not an HCK product model.
4. From heat load to unit: why the margin matters
Nameplate cooling capacity is measured at standard conditions. At 40 °C ambient with a restricted condenser side, real output falls below the nameplate figure. A 1.5× margin is the usual engineering practice:
2000 W × 1.5 = 3000 W. For indoor or mild outdoor duty, choose the HCK 3000W; with strong afternoon sun or ambient consistently near 40 °C, the 3500W is the safer pick. Both are production models and can be fitted to any cabinet type.
5. When this example does not apply
- Internal dissipation above 1400 W (several large drives): move straight to the 5000 W class.
- Battery enclosures: the battery itself is the heat source and temperature uniformity matters; assess separately.
- No usable wall for mounting, or no way to drain condensate.
6. How to verify after commissioning
- Run the equipment at full load and record the time to reach setpoint.
- Log duty cycle over three consecutive hot days; a flat 100% means the unit is short.
- Measure the top-to-bottom temperature spread; above 8 °C, check for airflow short-circuiting before upsizing.
- Confirm condensate actually drains instead of pooling in the cabinet base.
Match the example against site records and the next selection stops being a guess.
