Smaller and higher-power models are in development and coming soon.
Low-power cooling for small electrical cabinets and compact spaces. In development.
Ultra-high-power cooling for large prefab cabins and high-density scenarios. In development.
Detailed specifications of four models
| Spec | HCK-3K00022L | HCK-3K50022L | HCK-5K00022L | HCK-7K50022L |
|---|---|---|---|---|
| Cooling (W) | 3000 | 3500 | 5000 | 7500 |
| Heating (W) | 1000 | 1200 | 2000 | 3000 |
| Power | 220V±10%,50Hz | 220V±10%,50Hz | 220V±10%,50Hz | 220V±10%,50Hz |
| Cooling Power (W) | 1300 | 1300 | 1700 | 3300 |
| Refrigerant | R410A | R410A | R410A | R410A |
| Airflow (m³/h) | 1800 | 1800 | 2500 | 2800 |
| Noise (dB) | 60 | 61 | 65 | 70 |
| Protection | IP55 | IP55 | IP55 | IP55 |
| Operating Temp (°C) | -40~+55 | -40~+55 | -40~+55 | -40~+55 |
| Dimensions (mm) | 1150×485×250 | 1156×491×250 | 1350×620×310 | 1600×660×360 |
| Weight (kg) | 59 | 60 | 77 | 95 |
Three steps to the right cabinet AC
Determine cabinet size, internal heat load, and maximum ambient temperature.
Use Q=Q_equipment+Q_inflow to calculate required cooling capacity, add 20% margin.
Match to power range, confirm installation and electrical specs, then order.
Selection, cooling principle, specs & troubleshooting in one guide