HCK Cabinet Air Conditioner Model Matrix

Side-by-side cooling capacity, dimensions, noise and electrical data for the four production cabinet air conditioners. Sealed cabinets use closed-loop cooling rather than filtered fans.

Model specification matrix

SpecHCK-3K00022LHCK-3K50022LHCK-5K0022LHCK-7K50022L
Cooling (W)3000350050007500
Heating (W)1000120020003000
Power220V±10%,50Hz220V±10%,50Hz220V±10%,50Hz220V±10%,50Hz
Cooling Power (W)1300130017003300
RefrigerantR410AR410AR410AR410A
Airflow (m³/h)1800180025002800
Noise (dB)60616570
ProtectionIP55IP55IP55IP55
Operating Temp (°C)-40~+55-40~+55-40~+55-40~+55
Dimensions (mm)1150×485×2501150×485×2501350×620×3101600×660×360
Weight (kg)56607795

Noise 60-70 dB at 1 m; supply 220V +/-10% 50Hz; refrigerant R410A; protection IP55; comms RS485/Modbus. Refrigerant can be specified per project, subject to technical confirmation.

Selection guidance

HCK-3K00022L

3000W · 1150×485×250mm · 60dB · IP55

HCK-3K50022L

3500W · 1150×485×250mm · 61dB · IP55

HCK-5K0022L

5000W · 1350×620×310mm · 65dB · IP55

HCK-7K50022L

7500W · 1600×660×360mm · 70dB · IP55

Size the unit to cabinet heat load and available mounting space. One configuration can be frozen for repeat orders of the same project.

Request a quoteCustom configuration

Back to products

Related: Enclosure Cooling Reference — how the standard capacity ranges map to enclosure heat load.