1. The enclosure heat-load equation
A sealed electrical enclosure gains heat from three sources. The cooling unit has to remove the sum of them:
- Q_internal — waste heat dissipated by the components inside the cabinet: drives, power supplies, PLCs, relays, transformers and battery electronics. Use the manufacturer's dissipation figures and add them up in watts.
- Q_conduction — heat passing through the cabinet walls when the outside air is hotter than the target internal temperature. It depends on surface area, wall construction and the temperature difference.
- Q_solar — solar gain on outdoor cabinets and cabins. It depends on exposed surface area, surface colour, orientation and site location.
Unit conversion used in enclosure cooling specifications: 1 W = 3.412 BTU/hr. Multiply watts by 3.412 to express a heat load in BTU/hr.
Sizing should use the hottest realistic site condition, not the annual average. Where future component additions are expected, engineers commonly allow a margin above the calculated total. Confirm the final figure against the actual cabinet or cabin drawing.
2. Three cooling methods compared
No single method suits every duty. The choice follows whether the enclosure must stay sealed and whether the target temperature is below ambient.
| Method | Keeps enclosure sealed | Cools below ambient | Dust, salt, rain | Supplied by HCK |
|---|---|---|---|---|
| Filtered fan / ventilation unit | No — brings outside air in | No | Poor for outdoor or dirty sites | No |
| Air-to-air heat exchanger | Yes | No — only narrows the gap | Good | No |
| Closed-loop air conditioner | Yes | Yes | Good | Yes |
A closed-loop unit circulates internal air through an evaporator and rejects heat through a separate external circuit. The two air streams never mix, so an IP-rated or NEMA-rated enclosure can stay shut in rain, dust or salt air.
HCK supplies closed-loop cooling units. Where a filtered fan or heat exchanger is the right answer, that is a different purchase; this page does not claim those products.
3. Capacity selection
Standard production capacities: 3000W, 3500W, 5000W, 7500W.
- Calculate Q_total from section 1 and select a rated capacity that is not lower than that figure.
- Confirm the ambient design temperature, the cabinet or cabin drawing, the supply voltage and the mounting position before the cut-out is fixed.
- One room or cabin can contain several cabinets. Each cabinet can be treated separately, or the cabin space can be cooled as one volume, depending on the layout.
Closed-loop units are rated for a wide ambient window and can report internal temperature over RS485/Modbus for remote sites. Detailed electrical and mechanical parameters are in the specifications and the machine-readable product data.
4. Cabin-level and cabinet-level duty
A transportable switchroom or prefabricated cabin has two thermal layers that are often bought separately: the room or cabin space, and the sealed cabinets inside it. HCK units can serve either layer. The same four units can be fitted to different cabin types, selected from the heat load and the cabin drawing of each build.
Cabin-level duty is the primary application; a unit can also serve one sealed cabinet. HCK supplies the cooling units themselves. The design of a central room air-conditioning plant is not included.
5. Customization scope
- Cooling capacity. Any cooling capacity can be customized to the customer's requirement. The four capacities in section 3 are the standard production range; capacities outside that range are reviewed per project, subject to technical confirmation.
- Dimensions and cut-out. Case size, mounting holes, door or wall position, finish and nameplate text can follow the customer's series, subject to technical confirmation.
- Refrigerant. R410A is the standard charge. A different refrigerant named in a customer's specification is checked against that build and the regulations of the destination market by our engineers, subject to technical confirmation.
- Electrical and controls. Supply voltage, mounting style, control interface and RS485/Modbus monitoring can be configured per project, subject to technical confirmation.
Every customized item is confirmed by engineering against the actual build before release. This page states technical capability only; commercial terms are agreed separately for each project.
6. How to link or cite this page
This reference is published as ungated HTML and is free to link from a resources page, a training handout, a course reading list or a technical article. No permission request is needed for a normal editorial link.
Zhejiang Haocheng Industrial Control Equipment Co., Ltd. (HCK), "Enclosure Cooling Reference: Heat Load, Cooling Methods and Capacity Selection", https://www.zjhcc.com/en/enclosure-cooling-reference.html
Suggested anchor text: enclosure cooling heat-load reference, closed-loop cabinet air conditioner selection guide, or electrical cabinet cooling comparison table.
Prefer linking to this page rather than copying the tables, so readers always get the current figures. If you need a figure in a different unit or a machine-readable form, see products.json.