The largest opening is often at the bottom
Closed-loop cooling only works when the cabinet air stays separate from ambient air. In practice the weakest point is rarely the door gasket: it is the cable entry. An oversized cut-out, a gland plate drilled for cables that were later rerouted, or a bundle passing through an open slot all create a continuous air path.
What a leak costs
- Capacity: warm humid air entering continuously adds a load the original calculation never included.
- Contamination: dust and moisture reach terminals, which is precisely what a sealed enclosure was meant to prevent.
- Condensation: humid air meeting a cold internal surface can produce water where no drain was planned.
Specify the entry, not just the unit
For a project cabinet, the gland plate layout, cut-out dimensions and sealing method are part of the mechanical interface. Confirm the number and diameter of cables, reserve blanked positions for future circuits, and choose between a split plate, modular gland frame or sealed pass-through before the enclosure is punched. The cooling unit mounting footprint and the entry plate should be reviewed on the same drawing.