Heat-Budget Formula
Total capacity Qtot = Qint + Qcond + Qinf, then multiply by a 1.2–1.5 safety factor. Qint sums heat from VFDs, supplies and PLCs; Qcond is wall conduction plus solar gain; Qinf is door/seam infiltration.
Worked Example
| Item | Value |
|---|---|
| Internal heat Qint | 520W |
| Conduction+solar Qcond | 180W |
| Infiltration Qinf | 60W |
| Subtotal | 760W |
| ×1.25 safety | 950W |
Sizing Notes
- Use datasheet heat-loss, not rated power, for components.
- For direct sun or ambient >45℃, use factor 1.4+.
- Pick HCK-1000 (1000W) to cover 950W with margin.
查看 HCK 机柜空调产品 或 联系昊诚工控 获取选型方案。
4. A worked example, metric units
A plant integrator needs cooling for a drive cabinet in a foundry. The cabinet is 2.2 x 0.8 x 1.2 m, the ambient is 38 °C, the target internal temperature is 26 °C, and the equipment inside dissipates 2,960 W.
Step 1 — surface area
A = (2.2 x 0.8 + 2.2 x 1.2 + 0.8 x 1.2) x 2 = 39.5 m²
Step 2 — envelope heat gain
Q_env = 5.5 x A x ΔT = 5.5 x 39.5 x (38 - 26) = 2,607 W
Notice what this means: before a single drive is energised, the box itself is asking for 2.6 kW. On a small PLC panel that figure is routinely larger than the components.
Step 3 — component heat load
Q_i = 2,960 W, taken from drive and power-supply dissipation rather than from nameplate current.
Step 4 — apply the safety factor
Q_total = 1.1 x (2,960 + 2,607) = 6,124 W
Two 3,200 W units give 6,400 W of installed capacity — about 5 % spare, which is the right ballpark for a cabinet that will not change.
| Step | Calculation | Result |
|---|---|---|
| Surface area | (2.2x0.8 + 2.2x1.2 + 0.8x1.2) x 2 | 39.5 m² |
| Envelope gain | 5.5 x 39.5 x 12 | 2,607 W |
| Component load | given | 2,960 W |
| With safety factor | 1.1 x (2,960 + 2,607) | 6,124 W |
| Selected | two 3,200 W units | 6,400 W |
5. The same example converted to BTU / hour
Purchasing departments and US panel shops usually work in BTU/hr. The conversion is simple: BTU/hr = watts x 3.412.
- Envelope gain: 2,607 W x 3.412 = 8,894 BTU/hr
- Component load: 2,960 W x 3.412 = 10,100 BTU/hr
- With safety factor: 6,124 W x 3.412 = 20,897 BTU/hr
So the same cabinet is a ~21,000 BTU/hr application. If a supplier quotes you 300,000 BTU/hr for that panel, they sized it from the main isolator's current rating.
6. Why undersizing fails quietly
An undersized unit rarely fails in a way anyone notices on day one. It runs at 100 % duty for the whole hot season. And compressor capacity is at its worst exactly at 100 % duty — the refrigerant mass flow is fixed by the motor, so the heat it can lift falls away as ambient climbs. The result is a cabinet that gets hotter precisely in the worst week of the year, and a drive that trips on its own thermal cutoff long before the cooling unit would ever look wrong.
The expensive version of the same mistake is over-sizing from a nameplate rating. You pay for capacity that never gets used, and you get short cycling instead of spare cycling.
7. Site adjustments you must apply before selecting
| Condition | Effect on the calculation |
|---|---|
| Direct solar radiation on the cabinet | Add 10–30 % to the load |
| Ambient above 40 °C | Derate the selected unit by 10–20 % |
| Altitude above 1,000 m | Derate about 3 % per additional 100 m |
| Poor internal circulation | Add margin, and map the temperature distribution |
| Cabinet sealed against the building | Reduce the envelope term and cap the gain |
8. Five mistakes that account for most bad selections
- Sizing from full-load current instead of dissipation. Typically overestimates by 5–20x.
- Forgetting the envelope term entirely. On a large cabinet this is the dominant load.
- Applying one safety factor to the total and never to the site conditions.
- Ignoring duty cycle — assuming a unit rated for intermittent duty will run all summer.
- Placing the unit so its intake faces the cabinet's hot side, then blaming the capacity.
9. Two smaller units instead of one large one
Two half-size units are usually the better purchase, for three concrete reasons. They share the load so each runs part-time and lasts longer. They survive a single failure with degraded but non-zero cooling. And they can be staged — one unit for spring and autumn, both for a heat wave — which saves energy for most of the year.
10. Verifying the selection after commissioning
- Log the unit's duty cycle for one full week in the hottest month.
- Map internal temperature at the top, at the bottom and at the hottest component.
- If the spread is above 10 °C, the airflow is wrong, not the capacity.
- If duty is 100 % and the setpoint is being met, size up for next summer.
11. Reading the numbers back into the cabinet
A sizing calculation is only as good as the load it was given. The calculation returns a number in watts; the cabinet has to be built around that number. Three places where the two drift apart:
- The dissipation figures come from a datasheet at 25 °C. Drives dissipate more at high ambient because the semiconductor junction and the cooling fan both work harder.
- The envelope term assumes steady conditions. A cabinet opened for ten minutes an hour does not see the envelope at all; it sees ambient air inside the sealed volume.
- The safety factor gets applied twice, or not at all. One pass at 1.1 covers uncertainty in the load estimate; a second pass on top of that oversizes the unit and costs energy for a decade.
| Input | Typical source of error | Effect on the result |
|---|---|---|
| Component dissipation | Datasheet at 25 °C rather than at site ambient | Understates load in hot sites |
| Surface area | Inside concealed panels not counted | Understates envelope gain |
| Ambient | Recorded indoors when the cabinet sits outside | Understates everything |
| Safety factor | Applied twice, or omitted | Overstates, or understates capacity |
| Duty assumptions | Treated as continuous when the process is intermittent | Oversizes the unit |
12. Six sizing mistakes and how each one shows up
- Sizing from the drive's nameplate instead of its dissipated power. A 22 kW drive might dissipate 900 W. Selecting 22 kW of cooling is a 24-fold overestimate.
- Ignoring the envelope. In a small sealed cabinet at 40 °C ambient the box itself can be the largest heat source, larger than everything inside.
- Forgetting the safety factor. A load list is an estimate; the factor is what covers the error in the estimate.
- Selecting against room temperature, not the component's limit. A VFD may tolerate 40 °C and a battery 35 °C. Cooler is not automatically safer if it costs a permanently running compressor.
- Assuming the datasheet ambient. The quoted capacity applies at a stated ambient. A unit selected at 25 °C and installed outdoors in the Gulf will not hold its rating.
- Not checking the airflow path. A perfectly sized unit that recirculates its own heat performs like one half its size.
Every one of these is caught by the same three questions: what is the load, what is the ambient, and where does the air go.
