A door is a thermal event, not just an access point
Opening a sealed cabinet replaces conditioned air with ambient air in seconds. In dusty or humid sites that also brings contamination onto terminals. Whether the cooling unit should stop, alarm, or keep running is a project decision that belongs in the control description, not in a last-minute wiring change.
Three behaviours to define
- Stop on door open: avoids discharging cold air into the room and prevents a fan from drawing dust across live terminals; add a restart delay so the unit does not short-cycle.
- Alarm only: keep cooling running, but raise a dry contact or RS485/Modbus point so the control room sees an unclosed door.
- Event log: record opening duration for maintenance analysis, useful where repeated door access explains rising internal temperature.
Which of these is available depends on the controller and interface option chosen for the project. Confirm the required contacts, register map and fail-safe state (what happens if the door switch wire breaks) before the panel schematic is released.