Tightness is a prerequisite
A closed-loop cooling unit keeps cabinet air separate from ambient air. That assumption fails as soon as there is a permanent opening. Unlike a door opened briefly for maintenance, a fixed gap adds a continuous heat and moisture load that was never in the sizing calculation.
Three checks before handover
- Visual pass: door alignment, compressed gasket, gland plates, unused cut-outs, drain outlets and any field-drilled holes.
- Tracer pass: with the cabinet closed and the unit running, use a thin strip of paper or a smoke pencil around suspect joints to see whether air is drawn in. Keep the tracer away from live parts.
- Pressure or trend pass: where a low-pressure test is possible, log the decay; otherwise compare the internal temperature trend with ambient after the unit stops.
| Leak location | Typical sign | Action |
|---|---|---|
| Door gasket corner | Dust line, uneven compression | Reseat gasket, adjust hinge |
| Gland plate | Open spare holes | Blanking plate or sealed gland |
| Drain outlet | Warm air trace | Fit a one-way drain device |
Record the result as a commissioning baseline. A later change in internal temperature behaviour is much easier to interpret when the as-built tightness was documented at handover.