Two different currents
The steady running current describes normal operation. The brief current drawn at compressor start is higher, and it is the value that decides whether a protective device trips, whether a long cable drops too much voltage, and whether a generator or UPS can support the unit alongside the rest of the panel.
What to confirm before the schematic is released
- Protective device: check the trip curve against the starting characteristic, not only against the running current.
- Cable and voltage drop: long runs and high ambient in the duct both reduce the margin at start.
- Backup supply: on generator or UPS-fed sites, add the starting demand to the other loads that may restart at the same moment.
- Supply system: confirm frequency, voltage and earthing arrangement for the destination; a 60Hz North American supply can be specified per project.
Ask for the starting figure and the recommended protective device rating as part of the technical file. If several units sit on one feeder, a staggered start in the control logic avoids summing their starting currents into a single event — a control decision, not a hardware upgrade.
These are selection and configuration notes; final values depend on cabinet dimensions and site conditions. See product specifications or contact us for a project-specific configuration.