Sizing & Selection · 2026-11-11 · 昊诚工控

Measuring Cabinet Heat Load Instead of Guessing from Nameplates

Why the nameplate misleads

A drive rated at 30 kW does not put 30 kW of heat into the cabinet. Only the conversion losses become heat, typically a small percentage of the output. Sizing a cooling unit from the sum of nameplate ratings is the most common reason for a wildly oversized selection, while ignoring envelope gain is the most common reason for an undersized one.

A measurement procedure that survives review

TermWhere it comes fromCommon mistake
Internal dissipationLosses of installed componentsUsing nameplate power
Envelope gainAmbient minus internal temperatureOmitted on small sealed boxes
Solar gainSun on outdoor surfacesAdded twice or ignored

Record the ambient at which the measurement was taken. A capacity quoted at one ambient is not directly comparable with a measurement made at another, which is the first question to ask when comparing two proposals.

These are selection and configuration notes; final values depend on cabinet dimensions and site conditions. See product specifications or contact us for a project-specific configuration.

FAQ

Can I calculate the load without measuring?

Yes, from component loss data in the datasheets, but verify the calculation against a temperature log during commissioning.

How long until steady state?

Until the internal temperature curve flattens with the cabinet closed and the process at normal load. A short test usually underestimates the load.

Does ambient temperature matter at the measurement stage?

Yes. Envelope gain depends on the difference between ambient and internal temperature, so report the ambient alongside the result.