Where condensate comes from
During cooling, humid air passes over the evaporator and its water vapour condenses on the heat exchange surface. The water collects in the drain pan and leaves through the drain pipe. A restricted drain can lead to dripping and secondary condensation inside the cabin, and in worse cases water may seep into the cable layer and compromise electrical safety. Good drainage layout is therefore an often overlooked part of installation and inspection.
Layout essentials
- Keep the drain pan clean so that sludge and debris do not block the outlet;
- Maintain a continuous downward fall along the whole pipe, with no reverse slopes or low spots where water can sit;
- Fit a trap on negative-pressure sections so that odours and unconditioned air are not drawn back into the cabin;
- Insulate the condensate pipe along its full length to stop moisture forming and dripping on the outside;
- Terminate the drain at a nearby drain point or sump, never letting water drip onto equipment bases or into cable trenches.
| Check item | Acceptance point | Suggested interval |
|---|---|---|
| Drain pan | No standing water or blocked sludge | Monthly |
| Pipe slope | Continuous fall, no reverse slope | At installation and quarterly |
| Trap seal | Seal intact, not dried out | Quarterly |
| Pipe insulation | Covering intact, no damage | Quarterly |
| Drain outlet | Clear, no backflow or splashing | Monthly |
Winter freeze protection
In cold regions, water left in an idle drain pipe can freeze and split the pipe. Depending on site conditions, options include draining the standing water, adding trace heating, or shortening the exposed pipe run; the right measure depends on the local minimum ambient temperature and the actual layout. Before restarting, run a water-flow test and confirm the drain is clear and leak-free.