Enough cooling capacity, uneven air
A cabin unit can be sized correctly in watts and still leave one rack several degrees warmer than the rest. The reason is usually the air path, not the refrigeration circuit: supply air takes the shortest route back to the return opening, so the far end of the row never sees cold air.
Three checks before the build sheet is fixed
- Discharge direction: point the supply along the rack aisle, not straight at a wall or into the return.
- Return path: leave a continuous route behind or above the racks; a solid partition turns the aisle into a dead end.
- Unsealed openings: blank unused cut-outs and close cable gaps so conditioned air is not dumped into the ceiling void.
| Observed symptom | Likely cause | First check |
|---|---|---|
| One rack runs hot | Supply short-circuits to return | Smoke or thread test at the far end |
| Unit runs continuously | Return air already warm | Temperature at return vs setpoint sensor |
| Top of rack hottest | No vertical circulation | Discharge angle and baffle position |
For a project cabin the discharge direction, duct length, baffle position and alarm points are set against the rack layout before assembly, so the airflow arrangement is part of the documented configuration rather than a field adjustment.