What the imager actually shows
A thermal camera turns surface temperature into a picture. During commissioning it reveals where heat concentrates and whether the enclosure, the cooling unit and the cable routes are behaving as the layout intended. It finds problems a hand check misses because the surface looks normal.
Anomalies that should stop handover
- Local hot spots on busbars, terminals or cable lugs that exceed the temperature spread expected for the load.
- Uneven cabinet surfaces where one zone stays warm while neighbours stay cool, pointing to a blocked air path.
- Condenser or coil staining by heat that suggests restricted airflow rather than a clean exchange.
- Cable entry heating that signals a poor termination rather than the cooling design.
Build the acceptance record
Capture images at a defined load and ambient condition, label each with location, and keep them with the commissioning file. The same views taken later make a direct before-and-after comparison, so a slow drift shows up before it becomes a failure. Thermography is a check of behaviour, not a substitute for the electrical and cooling tests already required.
These are commissioning notes; the pass criteria depend on the cabin class and the equipment inside. See product specifications or contact us for a layout matched to the site.